Shopping security
The Foxboro FBM211 (Part Number: P0914TN) provides a high-density differential analog interface for the I/A Series Distributed Control System (DCS). This module specializes in collecting up to 16 independent 0–20 mA (including 4–20 mA) analog signals from field transmitters and sensors. By utilizing a differential input architecture, the FBM211 excels in environments where common-mode noise rejection is critical for signal integrity. We supply this unit as 100% Brand New original factory stock, ensuring laboratory-grade precision for oil & gas, chemical, and power generation monitoring.
| Item | Specification |
| Model / Part Number | FBM211 / P0914TN |
| Input Channels | 16 Differential Analog Inputs |
| Signal Range | 0–20 mA DC (Supports 4–20 mA) |
| Accuracy | ±0.05% of span |
| Resolution | 12-bit |
| Input Impedance | 250 Ω |
| Isolation | Galvanic; withstands 600 V AC for 1 minute |
| Communication | Redundant 2 Mbps Foxboro fieldbus |
| Power Supply | 24 V DC (+5%, –10%) |
| Operating Temperature | –20 °C to +60 °C (Module) / +70 °C (TA) |
| Dimensions | 15cm x 6.2cm x 15cm |
| Weight | 0.4 kg |
| Certifications | UL, CSA, CE, ATEX, Class 1 Div 2 / Zone 2 |
Superior Common-Mode Rejection: The differential input design allows the FBM211 to cancel out noise that appears on both signal leads. This capability proves essential in plants with heavy electromagnetic interference (EMI) or significant distances between the sensor and the I/O rack.
High-Precision Data Acquisition: An accuracy rating of ±0.05% of span ensures that critical process variables—such as flow rates and reactor pressures—remain within tight control limits. This precision directly supports optimized PID loop tuning and improved final product consistency.
Robust Galvanic Protection: Every channel features independent galvanic isolation capable of withstanding 600 V AC. This protective barrier prevents ground loops and ensures that a single high-voltage fault on one field device does not propagate through the fieldbus to damage the controller or adjacent modules.
Redundant Fieldbus Communication: The module interfaces with the redundant 2 Mbps Foxboro fieldbus, providing a secure data path. If one communication link fails, the system automatically switches to the backup path without losing process data or triggering unnecessary alarms.
Seamless Hot-Swap Replacement: Technicians can replace the P0914TN module while the baseplate is powered. This feature simplifies maintenance schedules and allows for hardware upgrades or repairs without interrupting the continuous operation of the rest of the control system.
What is the benefit of a "Differential" input compared to a single-ended input?
Differential inputs measure the voltage difference between two leads, which effectively ignores noise common to both. This makes the FBM211 far more resilient to electrical interference and ground potential differences than single-ended modules.
Can this module handle 4-20mA signals?
Yes. The 0–20 mA signal range fully encompasses standard 4–20 mA industrial signals. You can configure the software to scale these inputs appropriately for your DCS database.
Is the FBM211 P0914TN compatible with hazardous area installations?
The module carries ATEX and Class 1 Div 2 / Zone 2 certifications. When installed in a suitable enclosure and following site-specific safety regulations, it operates safely in environments where flammable gases or vapors may be present.
How does the 600V AC isolation protect my system?
The isolation barrier ensures that if field wiring accidentally contacts a high-voltage power line, the surge is contained at the module level. This protects the sensitive 24V DC logic and the communication bus from catastrophic failure.