The ABB DSDO110 (57160001-K/3) serves as a high-density digital output interface for the Advant OCS, Symphony Plus, and S100 I/O systems. This module provides 32 independent channels designed to drive field actuators, interposing relays, and indicator panels across a broad 24V to 48V DC voltage range. It facilitates precise command execution from the central controller to the plant floor, ensuring seamless automation in utility-scale power generation and heavy industrial processes.
The DSDO110 utilizes a rugged Euro-card design, allowing for high-density installation within standard ABB subracks.
| Attribute | Specification Details |
| Model Number | DSDO110 |
| Part Number | 57160001-K/3 |
| Output Channels | 32 Channels |
| Output Voltage Range | 24 V DC to 48 V DC |
| Output Current | 0.5 A per channel (Typical) |
| Isolation | Opto-isolated, 2500 V DC |
| System Compatibility | Advant OCS / Symphony Plus / S100 I/O |
| Power Consumption | +5V Modulebus: 45mA |
| Operating Temp | –25 °C to +55 °C |
| Dimensions | 324 mm x 22.5 mm x 225 mm |
| Weight | 0.375 kg |
| Country of Origin | Sweden |
The DSDO110 addresses the complex requirements of legacy system maintenance and modern process scaling:
Broad Voltage Flexibility: Unlike standard 24V-only cards, the DSDO110 operates effectively up to 48V DC. This wider window accommodates diverse field equipment and long cable runs where voltage drops might otherwise compromise signal integrity.
High-Integrity Isolation: 2500V opto-isolation decouples the sensitive logic of the Advant Master controller from field-side electrical transients. This protects your high-value CPU assets from catastrophic damage during field wiring faults or lightning-induced surges.
Optimal Heat Management: The Euro-card architecture facilitates efficient vertical airflow within the rack. This design prevents localized hotspots, extending the module's lifecycle even when all 32 channels operate at high duty cycles in non-climate-controlled environments.
Rapid Diagnostic Mapping: Integrated channel status monitoring allows the DCS to detect and report output discrepancies. Maintenance teams identify failed relays or broken field circuits directly from the HMI, eliminating the need for manual point-to-point hardware troubleshooting.
Is this unit 100% Brand New?
Yes. We supply the ABB DSDO110 57160001-K/3 as a 100% Brand New and Original product. Each board ships in its original factory-sealed packaging with full manufacturer-traceable quality.
What is the difference between the DSDO110 and the DSDO115A?
The DSDO115A (3BSE018298R1) serves as the modern replacement for the DSDO110 in 24V systems. While the DSDO110 supports up to 48V, the DSDO115A is optimized specifically for 24V applications where the maximum load current does not exceed 150 mA.
Can I install the DSDO110 while the rack is powered?
Standard ABB safety guidelines for the S100 I/O system recommend powering down the subrack before inserting or removing Euro-cards. This prevents potential backplane arcing and ensures the system bus correctly initializes the new hardware.
Does this module include the terminal base?
No. The DSDO110 refers to the plug-in Euro-card (Digital Output Board) itself. It requires a compatible S100 I/O subrack and its associated terminal units for field wiring integration.