Shopping security
The Allen-Bradley 1734-IE2I stands as a cornerstone for high-precision data acquisition within the POINT I/O family. This module provides two channels of isolated analog current inputs, specifically designed to interface with 4–20 mA or 0–20 mA transmitters. By offering channel-to-channel isolation, the 1734-IE2I eliminates ground loop interference, a common headache in distributed industrial environments. Its compact, modular form factor allows for seamless integration into DeviceNet, ControlNet, or EtherNet/IP networks through a POINT I/O adapter, making it an ideal choice for scalable process control and machine automation.
The 1734-IE2I delivers professional-grade accuracy through the following technical profile:
| Parameter | Specification Details |
|---|---|
| Number of Inputs | 2 Isolated Channels |
| Input Signal Range | 4–20 mA or 0–20 mA (User-Configurable) |
| A/D Resolution | 16-bit (0.32 µA/bit) |
| Absolute Accuracy | ±0.1% Full Scale at 25°C |
| Input Impedance | 250 Ω |
| Conversion Rate | 120 ms per channel |
| Temperature Drift | 5 ppm/°C |
| Power Consumption | 75 mA @ 5V DC (Bus Power) |
| Operating Temp | -40°C to +70°C (-40°F to +158°F) |
| Hazardous Location | Class I, Div 2, Groups A, B, C, D |
Total Channel Isolation: Unlike single-ended modules, the 1734-IE2I isolates each input channel from the backplane and from each other. This prevents noise cross-talk and protects your PLC processor from high-voltage transients on the field side.
16-Bit Precision Scaling: The high-resolution Delta-Sigma conversion allows for extremely granular monitoring of process variables. This is vital for applications like chemical dosing or pressure monitoring where minute changes signify critical process shifts.
Harsh Environment Durability: Rated for an impressive temperature range of -40°C to +70°C, this module thrives in unconditioned control cabinets and outdoor remote I/O stations where standard commercial electronics fail.
Bumpless Installation: The module snaps into a 1734-TB or 1734-TBS terminal base. Its "Removal and Insertion Under Power" (RIUP) capability allows technicians to replace modules without shutting down the entire I/O rack, significantly reducing system downtime.
Q: Is this 1734-IE2I module 100% Brand New or refurbished?A: We sell 100% Brand New, original Allen-Bradley factory stock. Each module comes in its original sealed box with the manufacturer's warranty and a guaranteed authentic serial number.
Q: Can I use the 1734-IE2I to measure voltage signals like 0-10V?A: No. The 1734-IE2I is strictly for current signals (mA). For voltage inputs, you should look for the 1734-IE2V (non-isolated) or other voltage-specific modules within the POINT I/O range.
Q: Does this module require a separate power supply for the loop?A: The module itself runs on POINT I/O bus power, but for 2-wire transmitters, you typically provide field power (24V DC) through the terminal base. 4-wire transmitters will use their own external power source while feeding the current signal into the IE2I.
Q: What is the correct Keyswitch Position for this module?A: You must set the 1734 terminal base keyswitch to Position 3 before inserting the 1734-IE2I. This mechanical interlock prevents the insertion of the wrong module type into a pre-wired base.
Ships within 48 hours · Estimated delivery Jul 11 - Jul 16
US$40
Get nowSign up to your membership to get coupons up to
15%
Get nowOpportunity to enjoy order discount up to 15% off
Top-Converting Item to Boost Your Average Order